UPS for Synology DS923+

The DS923+ is the most-installed 4-bay Synology — and the best-documented UPS pairing in homelab use.

Typical power draw: about 35–50 W with drives running. These are typical figures from manufacturer specifications and community reports — not measured by us. Check your exact combination in the checker before buying.

The DS923+ has the largest installed base of any 4-bay Synology, which is why its UPS pairings are also the best documented. The CyberPower CP1500PFCLCD is the most-reported combination in homelab forums: DSM detects it as a generic HID UPS, reads battery status, and shuts down cleanly. The APC BE600M1 is the budget pairing for a NAS and a router. A 4-bay DS923+ with four drives draws roughly 35–50 W, so even the smallest sensible UPS gives far more runtime than the two to four minutes a shutdown needs — the choice is about waveform and driver, not capacity. One warning still applies: DSM 7.4 broke USB UPS detection for many users, and 7.4.1 fixed most but not all cases. If your DS923+ stopped seeing its UPS after an update, read the fix page before buying anything new.

Which UPS fits the DS923+?

UPSSizeWaveformVerdictSource
CyberPower CP1500PFCLCD1500 VA / 1000 WPure sine waveWorksNUT HCL v2.8.3 + community reports
APC BE600M1600 VA / 330 WSimulated sineWorksNUT HCL v2.8.3
APC BR1500MS21500 VA / 900 WPure sine waveLikely worksNUT HCL v2.8.3
UGREEN US3000120 W DCDC outputNot compatibleUGREEN official list

How to set it up

Connect the USB cable that came in the box directly to the NAS — never through a hub. Enable UPS support in the operating system, choose USB UPS, and set the shutdown to trigger on low battery rather than after a fixed time: that rides out two-second flickers instead of shutting down for them. Then test it for real: pull the UPS input plug from the wall and watch the NAS enter Safe Mode or shut down. If it does not, the setup is not finished, however green the lights look.

What not to buy

Do not buy on VA alone. A 1500 VA unit at a 0.6 power factor carries 900 W — and your NAS draws a fraction of that. What matters is the waveform (pure sine wave for Active PFC supplies), the USB data connection, and whether your exact OS version has a driver for the model. The sizing tool works out the numbers; the checker answers the driver question.

See also: runtime calculator · NUT server setup · UPS not detected? Fix Finder

Reviewed by Dharmen Bhambu · Last reviewed 29 November 2026. No lab tests have been completed yet — every verdict on this site shows its source. See how we check and the test log.